A Slotted Cathodic Protection System for Bridge Decks

Report No: 85-R27

Published in 1985

About the report:

A non-overlay, slotted cathodic protection system was installed two years ago on a concrete bridge deck in Virginia. The design, installation, and operation of this system are fairly straightforward. A protective current density of 1.6 mA/ft2 (17 mA/m2) as determined by E-log I curves has been applied constantly on the deck. Various tests have shown that polarization of the structure has been achieved. After more than 18 months in service, the various components of this system appeared to be in good condition.

Disclaimer Statement:The contents of this report reflect the views of the author(s), who is responsible for the facts and the accuracy of the data presented herein. The contents do not necessarily reflect the official views or policies of the Virginia Department of Transportation, the Commonwealth Transportation Board, or the Federal Highway Administration. This report does not constitute a standard, specification, or regulation. Any inclusion of manufacturer names, trade names, or trademarks is for identification purposes only and is not to be considered an endorsement.

Authors

  • G. G. Clemeña

Last updated: January 16, 2024